30kVA / 35kVA / 40kVA / 40kVA
Mahindra Powerol’s ‘Spectro’ series of diesel gensets is one of the most silent gensets manufactured by the brand. It has sturdy wheels and a long handle which allows easy mobility of the genset.
Features :
- Compact Design
- Large Fuel Tank
- Longer Engine Life
- Low Maintenance Cost
- Preferred By All
Specifications :
PARAMETERS | DG MODELS | |||||||
---|---|---|---|---|---|---|---|---|
Duty (Standby/ Prime) | Prime | Stand By | ||||||
50 HZ PRIME | Rating(kVA) | 30 kVA | 30 kVA | |||||
Rated(kWe) | 24 | 24 | ||||||
Engine Model | 3445TCIGM-C2 | 3385 ELSTCGMC2 | ||||||
No of Phases | 1/3 | 1/3 | ||||||
No of Cylinders | 3 | 3 | ||||||
Output Voltage (V) | 230V/415V | 230V/415V | ||||||
Current (A) (1Phase / 3Phase) | 130.4/ 41.7 | 130.4/ 41.7 | ||||||
Power Factor (lagging) | 0.8 | 0.8 | ||||||
Frequency (Hz)/ RPM | 50/1500 | 50/1500 | ||||||
Governing class | A1 | A1 | ||||||
Starting system | 12 V DC Elec | 12 V DC Elec | ||||||
Fuel Tank Capacity (lits) | 115 | 115 | ||||||
Genset Dimension (LxWxH $$) (mm) Approx. |
3 Phase :- 2000 X 980 X 1280 1 Phase :- 2200 X 980 X 1280 |
3 Phase :- 2000 X 980 X 1280 1 Phase :- 2200 X 980 X 1280 |
||||||
Genset Weight (Kg), Appx | 3 Phase :- 935 1 Phase :- 1026 | 3 Phase :- 935 1 Phase :- 1026 | ||||||
Make | Mahindra | Mahindra | ||||||
Power Output# (HP) | 44 | 38.6 | ||||||
Aspiration | Turbocharged & Intercooled | Turbocharged | ||||||
No of Cylinders | 3 | 3 | ||||||
Bore x Stroke (mm) | 88.9 X 110 | 88.9 X 120 | ||||||
Displacement (cc) | 2048 | 2235 | ||||||
Fuel consumption @ 75% load (lit/hr) ^ | 5.7 | - | ||||||
Fuel consumption @ 100% load (lit/hr) ^ | 7.3 | - | ||||||
Lube oil specification | SAE15W40 CI4 | SAE15W40 CI4 | ||||||
Total Lube Oil capacity (lit) | 7 | 7 | ||||||
Lube Oil Consumtion (lit/hr) $ | 0.15% of Fuel Consumption | 0.15% of Fuel Consumption | ||||||
Lube oil change period (hrs.) |
300 hrs. for Oil Top Up 600 hrs. for Oil change |
300 hrs. for Oil Top Up 600 hrs. for Oil change |
||||||
Radiator coolant capacity (liter) | 9.5 | 9.5 | ||||||
Alternator | ||||||||
Enclosure Type | CG/LS | |||||||
Enclosure Type | IP23 | |||||||
Voltage regulation | ±1% | |||||||
Class of insulation | Class H | |||||||
Maximum Unbalanced Load across Phases | 25% |